Customization: | Available |
---|---|
Type: | T1+T2 |
Structure: | Zinc Oxide Arrester |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model
|
LY1-7/3S+1
|
SPD according to EN 61643-11 / IEC 61643-11
|
Type 1+2 / class I+II
|
Nominal a.c. voltage Un
|
230 / 400 V AC (50/60 Hz)
|
Max. continuous operating a.c. voltage [L-N] Uc
|
275 V AC (50/60 Hz)
|
Max. continuous operating a.c. voltage [N-PE] Uc
|
255 V AC (50/60 Hz)
|
Nominal discharge current (8/20μs) In
|
20kA
|
Maximum discharge current (8/20μs) Imax
|
50kA
|
Maximum impulse current (10/350μs) Iimp
|
7 kA / 50 kA (L-N / N-PE)
|
Voltage protection level Up
|
1,5 kV / 1,5 kV (L-N / N-PE)
|
Follow current extinguishing capability [N-PE] Ifi
|
100Arms
|
Response time tA
|
25ns (L-N)
|
Response time [N-PE] tA
|
100ns
|
Max. mains-side over-current protection
|
160A gL/gG
|
Short-circuit current rating ISCCR
|
25kA
|
Operating state / fault indication
|
Green ok / Red defect
|
Cross-sectional area (min.)
|
1.5 mm2 solid /flexible
|
Cross-sectional area (max.)
|
35 mm2 stranded / 25 mm2 flexible
|
For mounting on
|
35 mm DIN rail acc. to EN 60715
|
Application system
|
SPD is connected to TN and TT system
|
Remote signalling alarming mode
|
Normal: closed; Failure: open-circuit
|