Model
|
LY10-6V
|
LY10-12V
|
LY10-24V
|
LY10-48V
|
LY10-110V
|
||||
Rated working voltage Un
|
6V
|
12V
|
24V
|
48V
|
110V
|
||||
Max continuous working voltage Uc
|
8V
|
15V
|
36V
|
54V
|
130V
|
||||
Rated working current IL
|
1A
|
|
|
|
|
||||
Nominal discharge current In(8/20us)
|
5KA
|
|
|
|
|
||||
Max discharge current Imax(8/20us)
|
10KA
|
|
|
|
|
||||
Voltage protection level Up
|
≤15V
|
≤35V
|
≤65V
|
≤110V
|
≤500V
|
||||
Max transfer rate Vs
|
10Mbps
|
|
|
|
|
||||
Insert loss
|
≤0.2dB
|
|
|
|
|
||||
Response time tA
|
≤10ns
|
|
|
|
|
||||
Working temperature T
|
-40~+85
|
|
|
|
|