Gw: | 15.4kgs |
---|---|
in: | 20ka(8/20us) |
Imax: | 40ka(8/20us) |
Samples: |
---|
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Model
|
LY1-C40PV
|
SPD according to EN 61643-11 / IEC 61643-11
|
Type 1+2 / class I+II
|
Max. continuous operating pv. voltage Uc
|
1000V DC
|
Nominal discharge current (8/20μs) In
|
20kA
|
Maximum discharge current (8/20μs) Imax
|
40kA
|
Maximum impulse current (10/350μs) Iimp
|
6.25 kA
|
Impulse current totally (10/350μs) Iimp
|
12.5kA
|
Voltage protection level Up
|
3.6 kV
|
Follow current extinguishing capability [N-PE] Ifi
|
100Arms
|
Response time tA
|
25ns (L-N)
|
Matched fuse or circuit breaker
|
32A
|
Operating state / fault indication
|
Green ok / Red defect
|
Cross-sectional area (min.)
|
1.5 mm2 solid /flexible
|
Cross-sectional area (max.)
|
35 mm2 stranded / 25 mm2 flexible
|
For mounting on
|
35 mm DIN rail acc. to EN 60715
|
Switching capacity
|
AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A
|
Remote signalling alarming mode
|
Normal: closed; Failure: open-circuit
|
Suppliers with verified business licenses